INSTALLATION & OPERATION



INSTALLATION AND OPERATION INSTRUCTIONS

PREPARATION:
  1. Customer-Prepare a solid base, drainage and preflush water supply.

  2. Instruct all potential users in operation and location.

  3. Keep immediate area free of obstructions and paint the area a safety color.

  4. The potable water supply should be uninterruptable and never limited; 20 PSIG Min., 30 PSIG perferred and 60 PSIG Maximum.

  5. The emergency shower eye/face wash combination unit should be totally accessible from three sides without obstructions.
INSTALLATION:
  1. Uncrate and move to location area. End removal in easiest; simply cut strapping.

  2. Mount to prepared floor structure; 9" diameter, 8" bolt circle, and three equally spaced 3/8" mounting holes, except Models ES-1. Note: Unit base is solid steel and may be weled in place.

  3. Hook up pre-flushed 1-1/4" incoming water supply line; potable water is mandatory. Note: The greatest frequency problem is debris and rust, etc. in the incoming water supply line; 30 PSIG water pressure preferred, 60 PSIG Maximum Model ES-1 is supported by lower union and may require some type of column brace above the five foot level.

    Caution: Before the inlet water is turned on the overhead shower control arm should be in the shut off position; up all the way (about 45° angle). The eye/face wash unit should be in the shut off position; "push" flag pulled all the way forward toward the user position: parallel to the eye/wash nozzle plane.

  4. Remove (LB) condulet cover (2-4 screws) and hook up factory wiring using appropriate ware nuts or solder. Replace cover. Note: Since the water pipe itself is anticipated to be a perfect ground, the lights are generally, non-metalic, the third wire (ground) has not been provided in some instances. 110-120 volt, 60 HZ, single phase AC.

  5. OEM references and instructions are provided for options.
OPERATION:
  1. Activate the over head shower simply by pulling down on the pull rod.

  2. Shut off the over head shower by pushing up on the pull rod; approximately 45°.

  3. Activate the eye/face wash unit by pushing the aluminum flag or push plate horizontally away from the user toward the back of the shower.

  4. Shut off the eye/face wash unit by pulling the flag toward the user position parallel to the twin eye/wash spray nozzle plane.